We attended a 3 year old Floor Heating installation on a high quality home that was not working. After the customer was blocked by the original hydronic company we were contacted.
The heat pump was cycling on and off every 3-5 minutes. The wall thermostat was set to 26c and was struggling to reach 20c.
We found a huge 300w primary pump in the Monoblock heat pump and a tiny 30w secondary pump to feed the 14 internal floor circuits with an uncontrolled bypass loop.
This way out of balance pump fight would never work. Hydraulic separation like this is not necessary on slab floor heating and also increases costs and reduces efficiency. A concrete slab is a fantastic thermal battery.
We removed the small secondary pump and the bypass loop.
System was finally running perfectly when we departed with a return temperature delta of 5c. 3 years of inefficiency was solved in 3 hours. 