A fire-rated board isn't a fire-resisting wall. The whole system matters.
An FRL such as 60/60/60 (structural adequacy, integrity and insulation, in minutes) belongs to the whole wall as tested or listed, not to one sheet. Swap a board, a fixing or the spacing and it is no longer the tested system; only minor departures can be covered by an accredited laboratory's report. Inside 900 mm of a boundary the wall needs 60/60/60 tested from the outside, or 90 mm masonry or veneer with a 90 mm outer leaf. The ABCB recommends asking for the full test report, not just a certificate.
Order the wall system the test report describes, and build exactly that.
Send us the wall system before you order it.
Technical reference: NCC 2022 Vol. 2 A5G5 and Specification 1 S1C2 | ABCB Housing Provisions 9.2.3 | A5G3 Explanatory Information (guidance)
General builder education only. Site conditions, building classification, setbacks and the approved design can change the requirement.