Why VFD start frequency matters – and how to set it right
Most people assume a VFD starts from 0 Hz. In reality, when output frequency is 0, the motor lacks sufficient starting torque and cannot rotate. The motor only begins to accelerate after the output frequency reaches a certain value – that value is the start frequency.
✅ Three typical applications that require start frequency tuning:
① Multi‑pump parallel water supply systems
There is already water pressure in the pipes. Starting from 0 Hz makes it difficult for the pump to build up pressure – a certain start frequency is needed for a smooth start.
② High static friction loads
When the load has large static friction, starting from 0 Hz is hard. A properly set start frequency provides an initial impact to help the system break away from standstill.
③ Cone motors
During startup there is friction between the stator and rotor. The start frequency helps build enough magnetic flux quickly to maintain the air gap.
⚙️ How to set it right
Avoid the low‑frequency weak‑flux region – ensure enough starting torque
Do not set the start frequency too high, otherwise large current inrush may cause overcurrent trip
If overcurrent occurs during start, try extending the acceleration time
Read the full technical reference for parameter calculation methods:
👉 https://www.dlabb.cn/xinwendongtai/323.html
The frequency conversion speed controller is a device that converts the power frequency power (50Hz or 60Hz) into AC power of various frequencies to realize the variable speed operation of the motor.